Chapter 6  Control Modes of Operation  ASDA-B2 
6-30     Revision May, 2018 
 
P2-45    NCF3  Resonance Suppression (Notch Filter) 3 
Address: 025AH 
025BH 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section:  
Section 6.3.7 
 
 
Default: 1000 
 
Control 
Mode: 
ALL 
 
Unit: Hz 
 
Range: 50 ~ 2000 
 
Data Size: 16-bit 
 
Display 
Format: 
Decimal 
Settings: The third group of mechanism resonance frequency setting value. 
If P2-46 is set to 0, this function will be disabled. P2-23 and  
P2-24 are the first group of resonance suppression (Notch filter). 
 
P2-46    DPH3 
Resonance Suppression (Notch Filter) 
Attenuation Rate (3) 
Address: 025CH 
025DH 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section:  
Section 6.3.7 
 
 
Default: 0 
 
Control 
Mode: 
ALL 
 
Unit: dB 
 
Range: 0 ~ 32 
 
Data Size: 16-bit 
 
Display 
Format: 
Decimal 
Settings:  The third group of resonance suppression (Notch filter) 
attenuation rate. Set the value to 0 to disable the function of 
Notch filter.