ASDA-B2  Chapter 8  Communications 
Revision May, 2018     8-11 
RTU Mode:  
Command message (Master):   Response message (Slave): 
Slave Address  01H    Slave Address  01H 
Function 06H  Function 06H 
Starting data 
address 
02H (High)   
Starting data 
address 
02H (High) 
00H (Low)    00H (Low) 
Content of data 
00H (High)   
Content of data 
00H (High) 
64H (Low)    64H (Low) 
CRC Check Low  89H (Low)    CRC Check Low  89H (Low) 
CRC Check 
High 
99H (High) 
  CRC Check 
High 
99H (High) 
Note: Before and after the transmission in RTU mode, 10 ms of silent interval is needed. 
Example 3: function code 10H, write multiple words: 
The Master issues command to the 1
st
 Slave and writes 0BB8H and 0000H to the starting 
address 0112H. That is to say, 0112H is written into 0BB8H and 0113H is written into 
0000H. The maximum allowable data in one single access is 10. The Slave sends the 
response message to the Master after the writing is completed. The calculation of LRC 
and CRC will be described in next chapter.