Chapter 7 Parameters  ASDA-B2 
7-12  Revision May, 2018 
7.3 Parameter Description 
P0-xx Monitor Parameters 
P0-00★ 
  VER  Firmware Version   
Address: 0000H 
0001H 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section: N/A 
 
Default: Factory setting   
 
Control 
Mode: 
ALL 
 
Unit: - 
 
Range: - 
 
Data Size: 16-bit   
 
Format: Decimal 
Settings: This parameter only shows the firmware version of the servo 
drive. 
 
P0-01■ 
  ALE 
Alarm Code Display of Drive 
(Seven-segment Display)   
Address: 0002H 
0003H 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section: 
11.1, 11.2, 11.3 
 
 
Default: - 
 
Control 
Mode: 
ALL 
 
Unit: - 
 
Range: 0 ~ 0   
It only can be set to 0 to clear the alarm 
(Same as DI.ARST). 
 
Data Size: 16-bit   
 
Format: BCD 
Settings: Hexadecimal format: displays the alarm code 
0x0000: alarm clear (same as DI:ARST).
 
0x0000 ~ 0xFFFF: displays the alarm code (not writable). 
For the list of alarms, please refer to Section 9.1 Alarm of Servo 
Drive. 
Alarm of Servo Drive   
001: Over current 
002: Over voltage 
003: Under voltage (In default setting, the alarm occurs only 
when the voltage is not enough in Servo ON status; In Servo 
ON status, when it applies to power R, S, T, the alarm still 
will not be cleared. Please refer to P2-66.) 
004: Motor combination error (The drive corresponds to the 
wrong motor) 
005: Regeneration error