Chapter 11 Summary of Parameter SettingsCFP2000
11-1
Chapter 11 Summary of Parameter Settings
This chapter provides a summary of parameter (Pr.) setting ranges and defaults. You can set,
changed and reset parameters through the digital keypad.
NOTE
1) : You can set this parameter during operation
2) The following are abbreviations for different types of motors:
IM: Induction motor
PM: Permanent magnet synchronous AC motor
IPM: Interior permanent magnet synchronous AC motor
SPM: Surface permanent magnet synchronous AC motor
00 Drive Parameters
NOTE
IM: Induction Motor; PM: Permanent Magnet Motor
Pr. Parameter Name Settings Range Default
00-00 Identity code of the AC motor drive
5: 460V, 0.75 kW
7: 460V, 1.50 kW
9: 460V, 2.20 kW
11: 460V, 3.70 kW
13: 460V, 5.50 kW
15: 460V, 7.50 kW
17: 460V, 11.0 kW
19: 460V, 15.0 kW
21: 460V, 18.5 kW
23: 460V, 22.0 kW
25: 460V, 30.0 kW
27: 460V, 37.0 kW
29: 460V, 45.0 kW
31: 460V, 55.0 kW
33: 460V, 75.0 kW
35: 460V, 90.0 kW
93: 460V, 4.00 kW
Read
only
00-01
Display AC motor drive rated
current
Display by models
Read
only
00-02 Parameter reset
0: No function
1: Write protection for parameters
5: Reset kWh display to 0
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
9: Reset all parameters to defaults
(base frequency is 50 Hz)
10: Reset all parameters to defaults
(base frequency is 60 Hz)
0