Chapter 12 Description of Parameter SettingsCFP2000
12.1-05-6
Example: When Pr.05-30 = 76 MWh and Pr.05-29 = 150 kWh, Pr.05-28 = 400 Wh (or 0.4 kWh),
the accumulated total kilowatts of the motor per hour = 76 x 1000000 + 150 x 1000 + 40 =
76150400Wh = 76150.4 kWh
Accumulated Motor Operation Time (Min)
Default: 0
Settings 0–1439
Accumulated Motor Operation Time (Day)
Default: 0
Settings 0–65535
Use Pr.05-31 and Pr.05-32 to record the motor operation time. To clear the operation time, set
Pr.05-31 and Pr.05-32 as 00. An operation time shorter than 60 seconds is not recorded.
Induction Motor (IM) or Permanent Magnet Synchronous AC Motor Selection
Default: 0
Settings 0: IM (Induction motor)
1: SPM ( Surface permanent magnet synchronous AC motor )
2: IPM ( Interior permanent magnet synchronous AC motor )
Full-load Current for a Permanent Magnet Synchronous AC Motor
Default: Depending on
the model power
Settings Depending on the model power
Sets the full-load current for the motor according to motor’s nameplate. The default is 90% of the
drive’s rated current.
For example: The rated current of a 7.5 HP (5.5 kW) is 25 A. The default is 22.5 A.
The setting range is between 2.5–30 A. (25*10%=2.5 A and 25*120%=30 A)
Rated Power for a Permanent Magnet Synchronous AC Motor
Default: Depending on
the motor power
Settings 0.00–655.35 kW
Sets the rated power for the permanent magnet synchronous AC motor. The default is the drive’s
power value.
Rated speed for a Permanent Magnet Synchronous AC Motor
Default: 2000
Settings 0–65535 rpm
Pole number for a Permanent Magnet Synchronous AC Motor
Default: 10
Settings 0–65535