Chapter 12 Description of Parameter SettingsCFP2000
12.1-06-6
Related parameters: Pr.01-12, Pr.01-14, Pr.01-16, Pr.01-18 Acceleration Time 1–4, Pr.01-44
Auto Acceleration / Deceleration Setting, Pr.02-13–02-15 Multi-function Output Relay1–3.
Over-current Stall Prevention during Operation
Default: 120
Settings Light load: 0–130% (100%: drive’s rated current)
Normal load: 0–160% (100%: drive’s rated current)
This parameter only works in VF and SVC control modes.
This is a protection for the drive to decrease output frequency automatically when the motor
over-loads abruptly during constant motor operation.
If the output current exceeds the setting value for Pr.06-04 when the drive is operating, the drive
decreases output frequency (according to Pr.06-05) to prevent the motor from stalling.
If the output current is lower than the setting value for Pr.06-04, the drive accelerates
(according to Pr.06-05) again to the setting frequency.
Acceleration / Deceleration Time Selection of Stall Prevention at Constant Speed
Default: 0
Settings 0: By current acceleration / deceleration time
1: By the 1
st
acceleration / deceleration time
2: By the 2
nd
acceleration / deceleration time
3: By the 3
rd
acceleration / deceleration time