Chapter 12 Description of Parameter SettingsCFP2000
12.1-07-4
Current Limit for Speed Search
Default: 100
Settings 20–200% (100% corresponds to the light-load rated current of the drive)
The AC motor drive executes speed tracking only if the output current is greater than the value
set in Pr.07-09.
The maximum current for speed tracking affects the synchronous time. The larger the parameter
setting is, the faster the synchronization occurs. However, if the parameter setting is too large,
the overload protection function may be activated.