Chapter 7 Optional AccessoriesCFP2000
7-9
Non-fuse Circuit Breaker
Comply with UL standard: Per UL 508, paragraph 45.8.4, part a.
The rated current of the breaker shall be 1.6–2.6 times of the maximum rated input current of AC
motor drive.
Model Recommended non-fuse breaker [A]
VFD007FP4EA-41/-52/-52S 6
VFD015FP4EA-41/-52/-52S 6
VFD022FP4EA-41/-52/-52S 10
VFD037FP4EA-41/-52/-52S 15
VFD040FP4EA-41/-52/-52S 15
VFD055FP4EA-41/-52/-52S 20
VFD075FP4EA-41/-52/-52S 25
VFD110FP4EA-41/-52/-52S 35
VFD150FP4EA-41/-52/-52S 50
VFD185FP4EA-41/-52/-52S 60
VFD220FP4EA-41/-52/-52S 60
VFD300FP4EA-41/-52/-52S 90
VFD370FP4EA-41/-52/-52S 100
VFD450FP4EA-41/-52/-52S 125
VFD550FP4EA-41/-52/-52S 150
VFD750FP4EA-41/-52/-52S 200
VFD900FP4EA-41/-52/-52S 250
Table 7-5