3-5 Setting Up Parameters for the First Time | CP2000
9
Parameter
Display Text
Description of Parameter
Default
Value
Preferred
Value
00-32 Keypad
stop function
KPD STOP
ENABLE
This determines whether the
STOP key on the keypad is
active when the drive is
running in AUTO mode.
Parameter options:
0 STOP key disabled.
1 STOP key enabled
(preferred for safety)
0
1
Changes to Basic Parameters (01) group
Parameter
Display Text
Description of Parameter
Default
Value
Preferred
Value
01-11 Output
frequency lower
limit
Lower Bound
FREQ
This determines the
minimum speed of the drive
motor. It is important that
this speed is not too low to
prevent motor overheating.
0.00 Hz
10-15 Hz
01-12
Acceleration time
1
1st ACC Time
This is the time, in seconds,
for the drive to ramp up from
0 Hz to 60 Hz. It's important
that this time is not too fast,
or an overload fault will trip.
The factory default time is
too low.
10 secs
60 secs
01-13
Deceleration time
1
1st DEC Time
This is the time, in seconds,
for the drive to ramp down
from 60 Hz to 0 Hz. If this
time is set too low, an OVN
fault will occur. The factory
default time is too low for
large inertia loads like
centrifugal fans.
10 secs
60 secs

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit