Chapter 7 Optional AccessoriesCP2000
7-7
7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker
Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be ≥ 60°C and that for ACB should be
50°C. In the meanwhile, consider temperature derating for components with ON/OFF switch in
accordance with the ambient temperature of the on-site distribution panel.
230V Series
Frame Model
Light duty output
current [A]
Light duty input current
[A]
MC/ACB selection
[A]
A
VFD007CP23A
5 6.4 11
VFD015CP23A
7.5 9.6 18
VFD022CP23A
10 15 22
VFD037CP23A
15 22 40
VFD055CP23A
21 25 40
B
VFD075CP23A
31 34 55
VFD110CP23A
46 51 85
VFD150CP23A
61 67 105
C
VFD185CP23A
75 83 130
VFD220CP23A
90 99 150
VFD300CP23A
105 116 185
D
VFD370CP23A-00/21 146 146 225
VFD450CP23A-00/21 180 180 265
E
VFD550CP23A-00/21 215 215 330
VFD750CP23A-00/21 276 276 400
VFD900CP23A-00/21 322 322 500
460V Series
Frame Model
Light duty output
current [A]
Light duty input current
[A]
MC/ACB selection
[A]
A
VFD007CP43A-21
3.0 4.3 7
VFD015CP43B-21
4.2 6.0 9
VFD022CP43B-21
5.5 8.1 12
VFD037CP43B-21
8.5 12.4 22
VFD040CP43A-21
10.5 16 32
VFD055CP43B-21
13 20 32
VFD075CP43B-21
18 22 40
B
VFD110CP43B-21
24 26 40
VFD150CP43B-21
32 35 55
VFD185CP43B-21
38 42 65
C
VFD220CP43A-21
45 50 75
VFD300CP43B-21
60 66 105
VFD370CP43B-21
73 80 130
Table 7-7