Chapter 15 CANopen OverviewCP2000
15-28
15-6 CANopen LED Function
There are two CANopen flash signs: RUN and ERR.
RUN LED:
LED status Condition CANopen State
OFF Initial
Blinking
Pre-Operation
Single flash
ON
OFF
單次閃爍
200
ms
200
ms
1000
ms
Stopped
ON
Operation
ERR LED:
LED status Condition/ State
OFF No Error
Single
flash
One Message fail
ON
OFF
單次閃爍
200
ms
1000
ms
Double
flash
Guarding fail or heartbeat fail
ON
OFF
雙次閃爍
200
ms
200
ms
1000
ms
200
ms
Triple flash
SYNC fail
ON
OFF
雙次閃爍
200
ms
200
ms
200
ms
200
ms
1000
ms
200
ms
ON
Bus off

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit