Chapter 12 Description of Parameter SettingsCP2000
12.1-05-5
Accumulated Watt-hour for a Motor (W-hour)
Default: 0.0
Settings Read only
Accumulated Watt-hour for a Motor in Low Word (kW-hour)
Default: 0.0
Settings Read only
Accumulated Watt-hour for a Motor in High Word (MW-hour)
Default: 0
Settings Read only
Pr.05-28–05-30 record the amount of power consumed by the motors. The accumulation begins
when the drive is activated and the record is saved when the drive stops or turns OFF. The
amount of consumed watts continues to accumulate when the drive is activated again. To clear
the accumulation, set Pr.00-02 as 5 to return the accumulation record to 0.
The accumulated total watts of the motor per hour = Pr. 05-30 x 1000000 + Pr. 05-29 x 1000 + Pr.
05-28 Wh