Chapter 12 Description of Parameter SettingsCP2000
12.1-07-10
4: Stop by the 4
th
deceleration time
5: System deceleration
6: Automatic deceleration
When the multi-function input terminal is set to EF input (setting 10) or force to stop (setting 18)
and the terminal contact is ON, the drive stops according to the setting of this parameter.
Automatic Energy-saving Selection
Default: 0
Settings 0: Disable
1: Enable
When energy-saving is enabled, the motor acceleration and deceleration operate with full
voltage. During constant speed operation, it automatically calculates the best voltage value
according to the load power. This function is not suitable for fluctuating loads or loads which are
nearly full during operation.
When the output frequency is constant (that is, constant operation), the output voltage
decreases automatically as the load decreases. Therefore, the drive operates with minimum
multiplication of voltage and current (electric power).

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals