Chapter 16 PLC Function ApplicationsCP2000
16-4
6. When Pr.00-04 is set as 28, the displayed value is the value of PLC register D1043 (see figure
below):
Keypad KPC-CC01
Can display 0–65535
H 0.00Hz
A 0.00Hz
C _ _ _ _ _
7. In the PLC Run and PLC Stop mode, the content 9 and 10 of Pr.00-02 cannot be set nor be
reset to the default value.
8. The PLC can be reset to the default value when Pr.00-02 is set as 6.
9. The corresponding MI function will be disabled when the PLC writes to input contact X.
10. When the PLC controls converter operation, control commands will be entirely controlled by the
PLC and will not be affected by the setting of parameter 00-21.
11. When the PLC controls converter frequency commands (FREQ commands), frequency
commands will be entirely controlled by the PLC, and will not be affected by the setting of
Pr.00-20 or the Hand ON/OFF configuration.
12. When the PLC controls the drive’s operation, if the keypad Stop setting is valid, this will trigger
an FStP error and cause stoppage.

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals