4 Temperature Measurement Module DVP 04PT-E2
DVP-ES2 Module Manual
-3
DVP04PT-E2 Celsius (°C) Fahrenheit (°F) Input Impedance
Mode 0 (H’0000): PT100, °C
Mode 2 (H’0002): PT1000, °C
+8,000
+4,000
-1,800
-180
Digital output
Measured
temperature input
C
+800+400
C
C
Mode 0 (H’0000): PT100, °F
Mode 2 (H’0002): PT1000, °F
+14,720
+, 0736
-2,9 20
+1,472
+736
-292
F
F
Digital outpu
Measured
temperature input
F
Mode 1 (H’0001): NI 100, °C
Mode 3 (H’0002): NI 1000, °C
+1,700
+850
-800
+170+85
-80
C
C
Digital output
Measured
temperature input
C
Mode 1 (H’0001): NI 100, °F
Mode 3 (H’0002): NI 1000, °F
+3,380
+01,69
-1,120
+338
+169
-112
F
F
Digital output
Measured
temperature input
F
Temperature / d i gita l curve
(Default: Mode 0)
Mode 4 (H’0004): 0~300
3000
1500
300Ω
1
0Ω
Digital output
Measured input
impedance
0
Mode -1 (H’FFFF): Channel unavailable.
Average value and present value of input
channels will be displayed as 32,767(H’7FFF)
Operation/storage
1. Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2
2. Storage: -25°C ~ 70°C (temperature), 5 ~ 95%(humidity)
Vibration/shock immunity International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Power Supply
Max. rated power
consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 3W, supplied by external power source
4.6 CR (Control Register)
4.6.1 CR in DVP04PT-E2
DVP04PT-E2
CR# Save Register content
Description
#0 YES R Model name
Set up by the system:
DVP04PT-E2 model code = H’0082
#1 YES R Firmware version Display the current firmware version in hex.
#2 YES R/W CH1 Input mode setting
#3 YES R/W CH2 Input mode setting
#4 YES R/W CH3 Input mode setting
#5 YES R/W CH4 Input mode setting
Input mode: Default = H’0000. Take CH1 for example:
Mode 0 (H’0000): PT100: -180°C ~ 800°C
Mode 1 (H’0001): NI100: -80°C ~ 170°C
Mode 2 (H’0002): PT1000: -180°C ~ 800°C
Mode 3 (H’0003): NI1000: -80°C ~ 170°C
Mode 4 (H’0004): 0~300.
Mode -1 (H’FFFF): Channel 1 unavailable
#6 Reserved
#7 YES R/W Tempera t u r e unit sett i n g
Select the temperature unit (Celsius °C / Fahrenheit °F). Default =
H0(C)
#8 YES R/W CH1 average times
#9 YES R/W CH2 average times
#10 YES R/W CH3 average times
#11 YES R/W CH4 average times
Set average times at CH1 ~ CH4
Range = K1 ~ K100
Default = K10
#12 NO R Average temperature measured at CH1
#13 NO R Average temperature measured at CH2
#14 NO R Average temperature measured at CH3
#15 NO R Average temperature measured at CH4
Average temperature measured at CH1 ~ CH4.
Temperature u ni t: set in CR# 7
#16 ~ #19 Reserved