The cable gland is suitable for multi-core cable, if wiring is using single-core
cable with 3” flexible metal conduit, please follow below suggestions to avoid
water intrusion:
a. Insert the flexible metal conduit to cable gland and seal the conduit from both
inside and outside the wiring box and the gap between gland and conduit by
using duct seal to prevent living creature or moisture enter the wiring box.
b. Replace the cable gland to 3” EMT connector and seal the conduit from both
inside and outside the wiring box and the gap between gland and conduit by
using duct seal to prevent living creature or moisture enter the wiring box.
CAUTION !
conduit
conduit
a
b
Duct Seal
should not be loosen!
- Please make sure there is no gap between gland and cable.
- Please make sure the gland is tight after setup as shown below.
-
ATTENTION (for Taiwan use only)
-This inverter is compliant with the “Technical
Specification for Security Inspection of Solar
Inverter and Monitoring Units” required by BSMI.
- After completing the wiring operation and ensuring
the cover no longer needs to be opened, please
apply a brand new one-time-use security seal as
the picture shows. (item 10, Table 2-1) .
- We will not be liable or responsible for any security
incident caused by an improper application of the
sticker.
36