5.3 Replace Internal String Fuse
IEC listed IEC 60269-6
Table 5-2: Combiner Fuse Specification
Rated current
Rated voltage
Operating Class
Fuse Type
20 A
1500 V
Solar PV
10x85 ferrule
Typical Mfr
Mfr P/N
Littelfuse, Bussmann
SPXV 20, PV-20A10F85L
- Ensure DC and AC cables are always de-energized during the maintenance to
avoid the shock hazard risk!
- Before removing the fuses, please turn off DC switch and make sure the inverter
has stopped working, then remove the corresponding H4 Plus connector.
DANGER : ELECTRICAL HAZARD!!