Table 6-3A: Warning Codes (Field warning) & Messages
Message Description Action
1. DC Connectors polar is incorrect
2. String current monitoring function
is failure
1. Check the polarity of PV connection
2. Restart DC switch and AC breaker
3. Contact customer service for
technical support
De-rating
(W07)
String fault
(W08)
1. Over temperature
2. Power Limit function
3. Power vs. Frequency function
4. P(V) function
5. Grid Voltage low
6. Solar Voltage low
7. Solar Voltage High
8. Ramp up function
1. Check the installation ambient and
environment
2. Check Grid Code & Grid setting
3. Check the utility frequency on the inverter
terminal
4. Check the utility voltage on the inverter
terminal
5-1. Check the utility voltage on the inverter
terminal
5-2. Check reactive power setting
6. Check the Solar voltage on the inverter
terminal
7. Check the Solar voltage on the inverter
terminal
8. Check Ramp up setting
6.3 Warning Codes (Field Warning)
Table 6-4A: Warning Codes (inverter warning) & Messages
Message Description Action
Fan Fail
(W11)
1. One or more fans are locked
2.
One or more fans are defective
3. One ore more fans are
disconnected
1. Remove the object that stuck in the fan(s)
2. Check the connections of all fans
3. Replace the defective fan(s)
Ext Fan Fail
Int Fan Fail
DC SPD Fault
(W17)
AC SPD Fault
(W18)
1. One or more SPD are defective
2. One or more SPD are
disconnected
1. Replace the defective SPD
2. Check the connections of SPDs
Aux Power Fault
(W19)
The Aux-Power defective
Contact customer service for
technical support
6.4 Warning Codes (Inverter Warning)
Contact customer service for
technical support
Contact customer service for
technical support
String COMM
Fault
(W22)
String monitor communication fail
String Current
Low
(W23)
Disconnect in DC connectors
1. Check String Connector and Fuse
2. Contact customer service for
technical support
84
Error Message and Trouble Shooting

Table of Contents