EasyManua.ls Logo

Delta M125HV - Connection

Delta M125HV
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.6.2 RS-485 Connection
INFORMATION
* Screw torque: 0.59 Nm
(cross-section: 0.5~1.5 mm²)
strip from shielding layer
shielding layer
Insulation Tape
When the RS-485 cable needs to be grounded, please follow the steps below.
1. strip a wire from the shielding layer and properly insulate it
2. crimp the insulated wire to the Y-type lug and fix it in position A
SNYBL1-4
A
The pin definition for the RS-485 terminal block is shown in
Table 3-4.
- Pins 1 and 2 provide a 12VDC bus for use with accessories.
(If use of 12VDC bus is necessary, place switch 1 in ON position.)
- Pins 3 and 5 are both connected to the DATA+ input.
- Pins 4 and 6 are both connected to the DATA
-
input.
These connections allow easy daisy-chaining of multiple inverters.
A 120ohm bus termination resistor and associated control switch are located on
the communication board (Figure 3-22), refer to
Table 3-5
for the switch function.
Different RS-485 connection scenarios require different set up for the 120ohm
bus termination resistor.
When several inverters are cascaded (i.e., "daisy-chained") only the last inverter
in the chain must have its bus termination resistor switched ON.(Figure 3-25)
If the length of any RS-485 bus is greater than 610m, the use of Belden 3105A
cable (or eq.) is recommended to insure communication quality.
• The length of RS-485 cable is recommended to be less than 30m in general.
Table 3-4: RS-485 Terminal block wiring
- In order to have good transfer quality, twisted-pair wire is recommended to be
used as communication cable.
ATTENTION
Pin Function
1 VCC (+12V)
2 GND (It is not the PE)
3 DATA+
4 DATA-
5 DATA+
6 DATA-
1 2 3 4 5 6
VCCGND D+ D- D+ D-
45
Installation

Table of Contents

Related product manuals