Model
DC Input
Table 7-1A: Specifications
AC Output
Occasionally Max. voltage
Operating voltage range
MPP voltage range
Rated voltage
MPP tracker
Connection
Surge protection
String current monitoring
DC switch
Max. operating current
Max. allowable array Isc
M125HV_111
1500V *
1
320A
860
–
1500V
860
–
1350V *
2
1050V
20 pairs of H4 series connectors
*
3
1
150A
String fuse provisioned 20A/1500V PV fuses
Max. output power
Max. output current
Rated voltage
Operating frequency range
Power factor
Surge protection
T.H.D
Connection
135A
Operating voltage range
Rated output power
125kW / 140kVA
125kW / 125kVA
Max. inrush current
Max.
output overcurrent protection
175A
Max.
output fault current
(rms)
160A
300A, 100μs
Vac600V: -36% ~ +15%
3P/PE, 600Vac
50/60Hz ±5Hz
0.8 ind ~ 0.8 cap adjustable (1~0.9 at maximum power)
Ring terminal lug with Terminal block (Max. 185mm
2
Cu or Al wire)
Night time consumption
*
4
< 3.5W
Type II SPD (option type I, type I+II)
<3%
7 Technical Information
Type II SPD (option type I, type I+II)
YES
YES
7.1 Technical of M125HV_111
*
1
Maximum withstands voltage is 1600Vdc. However, the inverter will stop operating when the input voltage is above 1500Vdc.
*
2
Ambient < 25°C : 860~1350V;Ambient < 40°C : 860~1250V
*
3
Accessories H4 Plus for field wiring, suitable size : 4 / 6 / 10(optional) mm² copper conductor
*
4
Night time consumption with standby communication.
85
Technical Information