Model
Efficiency
Peak efficiency
Euro efficiency
M125HV_111
>99 %
98.7 %
900 x 663 x 334
Information
Communication
Indicator
RS-485 (Delta / Sunspec) , Bluetooth
Regulation
Enedis-PRO-RES_64E
UTE C 15-712-1
VDE AR-N 4110
TRF_EN50549-2_2019a
EN 61000-6-2
EN 61000-6-3
IEC 62109-1/-2
IEC 61439-2
IEC 61727
IEC 62116
IEC 62910
IEC 62109
LED
(Grid, Alarm, COMM.)
General Data
Operating temp. range
Protection level
Operating elevation
-30°~60°C (>50°C de-rating)
Max. inverter backfeed current
to the array
0A
Pollution degree 3
Overvoltage category AC output :III, DC Input :II
Protective class I
AC connection type
Ring terminal lug with Terminal block (Max. 185mm
2
Cu or Al wire)
Smart inverter functionality
Voltage/Frequency Ride through, Volt/Var, Volt/Watt,
Power curtailment, Frequency/Watt
IP65 (Electronics)
<3000m, Outdoor, wet locations
Forced air cooling with Smart Fan control
Relative humidity
0% – 100% non-condensing.
Cooling
80
Dimension (W x H x D, mm)
71.5 dBA @1m, Amb25°C
Noise
Weight (kg)
Table 7-1B: Specifications
86