- When 30A string fuses are utilized do NOT use input 2347
10141516 and 19 on either MPPT channel.
CAUTION !
M125HV_111 is compatible with 1500V/30A CE listed fuse, however, the designer
must be beware of the following requirements:
The max Isc-stc of a connected array (sum of all paralleled strings) cannot
exceed the rated Isc limit of the inverter, that is no more than 320A total.
Because of internal current limitations and higher string currents allowable
with 30A fuses, inputs 234710141516 and 19 must NOT be
used.
■ DC Side Y connection
-
01
-
02
-
03
-
04
-
05
-
06
-
07
-
08
-
09
-
10
-
11
-
12
-
13
-
14
-
15
-
16
-
17
-
18
-
19
-
20
Fuse Board
-
Fuse Board +
+01 +02 +03 +04 +05 +06 +07 +08 +09 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20
Switch 2 Switch 1
Recommend fuse models
1. Vendor: Mersen Vendor P/N: HP15M30
2. Vendor: EATON(Bussmann Series) Vendor P/N: PV-30A10F85L
3. Vendor: Littelfuse Vendor P/N: SPXV 30
40