bit 0: When the operating pump is failed, whether it switches to an alternative pump or not
0: Stop all pump action
1: Switch to an alternative pump
Example: bit0 = 0, when an error occurs to the running pump, all pumps stop.
bit0 = 1, when an error occurs to the running pump, switch the erroneous pump to an
alternative one.
bit 1: During the operation, stop or standby after resetting from error
0: Set the erroneous pump to be in a standby status after reset (the pump receives the RUN
command)
1: Set the erroneous pump to be in a stop status after reset (the pump does not receive the
RUN command).
Example: bit1 = 0, after you reset the erroneous pump, it can be set running through the
controller
bit1 = 1, after you reset the erroneous pump, it cannot be set running through the controller
until the master pump gives a STOP command.
bit 2: Whether the master pump receives the RUN command or not when the pump has an error
0: The master pump does not receive RUN command when an error occurs to the running
pump
1: The master pump can choose an alternative pump to run when an error occurs to the
running pump
Example: bit 2 = 0: when an error occurs to Pump #2, the master pump does not accept the
RUN command.
bit 2 = 1: when an error occurs to Pump #2, the master pump receives the RUN command
and chooses to run with an alternative pump.
This parameter is only valid in AUTO mode.