Chapter 10 Digital Keypad|CFP2000
10-25
If there has User Parameter settings, when back to Application Selection
List page, press ENTER it will display
the current application as " User
Parameter “, then press ENTER again, it will appear the previous setting
parameters.
Example:Select Fan Application
In Pr. Setup page,useST key to select
13:Application Selection List,then press
.
UseSTkey to select 00:Application
Selection List,then press
.
It is showing 13-00 parameter value=0(no
function) ,useST key to adjust the number
to 3: Fan,then press
to load the
relevant parameters of the fan application.
Back to main page,use ST key to select
14:Application Selection List,then
press
.
It shows there are 33 default parameters
setting in fan application,then press
.
Fan
No. Pr. Explanation Settings
1 00-11 Control of Speed Mode System Definit
on
2 00-16 Load Selection System Definition
3 00-17 Carrier Frequency Factory Setting
4
00-20
Source of Master Frequency Command
(AUTO)
System Definition
5 00-21
Source of the Operation Command (AUTO)
System Definition
6 00-22 Stop Method System Defin
tion
7 00-23 Control of Motor Direction System Definition
8
00-30
Source of the Master Frequency Command
(HAND)
System Definition