Chapter 10 Digital Keypad|CFP2000 Series
10-26
9 00-31
Source of the Operation Command (HAND)
System Definition
10
1-00
Max. Operation Frequency
Factory Setting
11 01
01
Output Frequency of Motor 1
Factory Setting
12 01-02
Output Voltage of Motor 1
Factory Setting
1
01-03
Mid-point Frequency 1 of Motor 1
Factory Setting
14 01-04
Mid-point Voltage 1 of Motor 1
Factory Setting
15 01-05
Mid-point Frequency 2 of Motor 1
Factory Setting
16 01-06
Mid-point Voltage 2 of Motor 1
Factory Setting
17 01-07
Min. Output Frequency of Motor 1
Factory Setting
18 01-08
Min. Output Voltage of Motor 1
Factory Setting
19 01-10
Output Frequency Upper Limit
System Definition
20 01-11
Output Frequency Lower Limit
System Definition
21 01-12
Accel. Time 1
System Definition
22 01-13
Decel Time 1
System Definition
23 01-43
V/F
Curve Selection
System Definition
24 02-05
Multi-function Input Command 5 (MI5)
System Definition
25 03-00
Analog Input Selection (AVI)
System Definition
26 03-01
Analog Input Selection (ACI)
System Definition
27 03-28
AVI1 Selection
System Definition
28 03-29
ACI Selection
System Definition
29 03-31
AFM2 Output Selection
System Definition
30 03-50
Analog Input Curve Selection
System Definition
31 07-06
Restart after Momentary Power Loss
System Definition
32 07-11
Number of Times of Auto Restart After
Fault
System Definition
33 07-33
Auto restart internal of Fault
System Definition
UseST key to select parameter from
01~33,after selecting the parameter you
want to change(e.g. 01:Control of Speed
Mode) ,then press
.
It is showing 00-11 parameter
value=0(VF(IM V/F control)) ,useST key to
adjust the number to 2 SVC(IM/PM
Sensorless vector control),then press
,
it will change to SVC control.
There are 33 parameters in fan application,if you want to adjust or add
parameters,please select Pr. 13-01~33 for parameter adjustment; or select
Pr. 13-34~99 for new parameter setting in parameter group 13.