EasyManua.ls Logo

Delta VFD007FP4EA-41 - Page 195

Delta VFD007FP4EA-41
404 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 11 Summary of Parameter SettingsCFP2000 Series
11-21
Pr.
Explanation
Settings
Factory
Setting
06-38
Motor Speed in rpm at
Malfunction
-32767~32767 rpm
Read
only
06-39
Reserved
06-40
Status of Multi-function Input
Terminal at Malfunction
0000h~FFFFh
Read
only
06-41
Status of Multi-function Output
Terminal at Malfunction
0000h~FFFFh
Read
only
06-42
Drive Status at Malfunction
0000h~FFFFh
Read
only
06-43
Reserved
06-44
STO Latch Selection
0STO Latch
1STO No Latch
0
06-45
Treatment to Output Phase Loss
Detection (OPHL)
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
3
06-46
Deceleration Time of Output
Phase Loss
0~65.535 sec
0.500
06-47
Current detection level of output
phase loss
0.00~100.00%
1.00
06-48
DC Brake Time of Output Phase
Loss
0~65.535sec
0.000
06-49
LvX Auto Reset
0: Disable
1: Enable
0
06-50
Time for Input Phase Loss
Detection
0.00~600.00 sec
0.20
06-51
Reserved
06-52
Ripple of Input Phase Loss
0.0~320.0 Vdc
60.0
06-53
Treatment for the detected Input
Phase Loss (OrP)
0: warn and ramp to stop
1: warn and coast to stop
0
06-54
Fault Code Record Index
0~6
Read
only
06-55
Derating Protection
0: constant rated current and limit carrier wave by
load current and temperature
1: constant carrier frequency and limit load current
by setting carrier wave
2: constant rated current(same as setting 0), but
close current limit
0
06-56
PT100 Detected Level 1
0.000~10.000V
5.000
06-57
PT100 Detected Level 2
0.000~10.000V
7.000
06-58
PT100 Level 1 Frequency
Protect
0.00~599.00Hz
0.00
06-59
PT100 activation level delay time
0~6000 sec.
60
06-60
Software Detection GFF Current
Level
0.0~6553.5 %
60.0
06-61
Software Detection GFF Filter
Time
0.00~655.35 sec
0.10
06-62
Reserved
06-63
Fault Record 1 (Day)
0~65535 days
Read
only
06-64
Fault Record 1 (Min)
0~1439 min
Read
only
06-65
Fault Record 2 (Day)
0~65535 days
Read
only

Table of Contents