Chapter 11 Summary of Parameter SettingsCFP2000 Series
11-22
Pr.
Explanation
Settings
Factory
Setting
06-66
Fault Record 2 (Min)
0~1439 min
Read
only
06-67
Fault Record 3 (Day)
0~65535 days
Read
only
06-68
Fault Record 3 (Min)
0~1439 min
Read
only
06-69
Fault Record 4 (Day)
0~65535 days
Read
only
06-70
Fault Record 4 (Min)
0~1439 min
Read
only
06-71
Low Current Setting Level
0.0 ~ 100.0 %
0.0
06-72
Low Current Detection Time
0.00 ~ 360.00 sec.
0.00
06-73
Treatment for low current
0 : No function
1 : Warn and coast to stop
2 : Warn and ramp to stop by 2nd deceleration time
3 : Warn and operation continue
0
06-74
~
06-75
Reserved
06-76
dEb motion offset setting
0~200.0 Vdc
40.0Vdc
06-77
~
06-79
Reserved
06-80
Fire mode
0: No function
1: Forward operation
2: Reverse Operation
0
06-81
Operating Frequency when
running Fire Mode(Hz)
0.00 to 599.00Hz
60.00
06-82
Bypass Fire Mode enabled
0: Disable Bypass
1: Enable Bypass
0
06-83
Delayed Time when Bypass Fire
Mode
0.0 to 6550.0 sec
0.0
06-84
Auto reset counter of Fire Mode
0~10
0
06-85
Length of time to reset
auto-counter (seconds)
0.0 to 6000.0 sec
60.0
06-86
Fire mode motion
0: Open loop control & manual reset fire mode
1: Close loop control & manual reset fire mode
2: Open loop control & auto reset fire mode
3: Close loop control & auto reset fire mode
0
06-87
Fire mode PID set point
0~100.00% (according to Pr.01-00 Max. operation
frequency)
0.0