Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-03-22
Status of PLC Output Terminal
Factory Setting: 0000h
Settings 0~65535
Monitor the status of PLC analog output terminals
P.03-30 shows the external multi-function output terminal that used by PLC.
AFM 1
10325476
NOTE
2 = 1 28 2 =6 4
2 = 3 2 2
4
= 1 6 2 = 8
2 =4 2 =2 2 =
1=OFF
For Example:
If the value of Pr.03-30 displays 0002h(Hex), it means AFM1and AFM2 are used by PLC.
Bit
AFM 1
10000000
22222222
7 6 5 4 3 2 1 0
Display value
2=1x2 +0x2
= bi t 1x 2 +bi t 0x2
10
10
AFM 2
Weights
0=Not used by PLC
1=Used by PLC
AFM2 Output Selection
Factory Setting: 0
Settings 0: 0-20mA output
1: 4-20mA output
AFM1 DC output setting level
AFM2 DC Output Setting Level
Factory Setting: 0.00
Settings 0.00~100.00%
Pair with Multi-Function Output : 23, Pr03-32 and Pr03-33 can output constant AFM voltage.
Set Pr03-32 between 0 to 100%.00 to correspond to 0~10V of AFM1
Set Pr03-33 between 0 to 100.00 % to correspond to 0~10V of AFM2
AFM1 Output Selection
Factory Setting: 0
Settings 0: 0-20mA output
1: 4-20mA output