Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-06-14
Status of Multi-function Input Terminal at Malfunction
Factory Setting: Read only
Settings 0000h~FFFFh
Status of Multi-function Output Terminal at Malfunction
Factory Setting: Read only
Settings 0000h~FFFFh
When malfunction occurs, user can check the status of multi-function input/output terminals. If it
happens again, it will overwrite the previous record.
Drive Status at Malfunction
Factory Setting: Read only
Settings 0000H~FFFFh
When malfunction occurs, please check the drive status (communication address 2119H). If
malfunction happens again, the previous record will be overwritten by this parameter.
Reserved
STO Alarm Latch
Factory Setting: 0
Settings 0: STO alarm Latch
1: STO alarm no Latch
Pr.06-44=0 STO Alarm Latch: after the reason of STO Alarm is cleared, a Reset command is
need to clear STO Alarm.
Pr.06-44=1 STO Alarm no Latch: after the reason of STO Alarm is cleared, the STO Alarm will be
cleared automatically.
All of STL1~STL3 error are “Alarm latch” mode (in STL1~STL3 mode, the Pr.06-44 function is no
effective).
Treatment to Output Phase Loss (OPHL)
Factory Setting: 3
Settings 0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
The OPHL protect will be active when the setting is not 3.
Deceleration Time of Output Phase Loss
Factory Setting:0.500
Settings 0.000~65.535 sec
Current detection level of output phase loss
Factory Setting:1.00
Settings 0.00~100.00%