EasyManua.ls Logo

Delta VFD007FP4EA-41 - Page 355

Delta VFD007FP4EA-41
404 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-09-13
1: Decoding Method 2 (60xx)
Decoding Method 1 Decoding Method 2
Source of
Operation
Control
Digital Keypad Digital keypad controls the drive action regardless decoding method 1 or 2.
External Terminal External terminal controls the drive action regardless decoding method 1 or 2.
RS-485 Refer to address: 2000h~20FFh Refer to address: 6000h ~ 60FFh
CANopen Refer to index: 2020-01h~2020-FFh Refer to index:2060-01h ~ 2060-FFh
Communication Card Refer to address: 2000h ~ 20FFh Refer to address: 6000h ~ 60FFh
PLC PLC commands the drive action regardless decoding method 1 or 2.
Internal Communication Protocol
Factory Setting: 0
Settings 0: Modbus 485
-1: Internal Communication Slave 1
-2: Internal Communication Slave 2
-3: Internal Communication Slave 3
-4: Internal Communication Slave 4
-5: Internal Communication Slave 5
-6: Internal Communication Slave 6
-7: Internal Communication Slave 7
-8: Internal Communication Slave 8
-9: Reserved
-10: Internal Communication Master
-11: Reserved
-12: Internal PLC Control
When it is defined as internal communication, see CH16-10 for information on Main Control
Terminal of Internal Communication.
When it is defined as internal PLC control, see CH16-12 for Remote IO control application ( by
using MODRW).
Reserved
PLC command force to 0
Factory Setting0000h
Setting
0000~FFFF
It defines the action that before PLC scans time sequence, the frequency command or speed
command needs to be cleared as 0 or not.
Bit Explanation
Bit0 Before PLC scan, set up PLC target frequency=0
Bit1 Before PLC scan, set up the PLC target torque=0
Bit2 Before PLC scan, set up the speed limit of torque control mode=0

Table of Contents