Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-09-16
Reserved
BACnet Max Address
Factory Setting: 127
Settings 0~127
BACnet Password
Factory Setting: 0
Settings 0~65535
~
Reserved
Identifications for Communication Card
Factory Setting: 0
Settings 0: No communication card
1: DeviceNet Slave
2: Profibus-DP Slave
3: CANopen Slave/Master
4: Modbus-TCP Slave
5: EtherNet/IP Slave
6~8: Reserved
Firmware Version of Communication Card
Factory Setting: ##
Settings Read only
Product Code
Factory Setting: ##
Settings Read only
Different communication cards have their own product codes with different value.
DeviceNet: As it connects to different kind of motor drive, it will have different product code.
Profibus: ID number of a communication card. Each Profibus selling in the market must apply
for an ID number at the Profibus International to be a unique product.
Fault Code
Factory Setting: ##
Settings Read only
For more information about Fault codes, refer to Pr. 06-17~06-22 and Chapter 14.
~