Chapter 5 Main Circuit Terminals|CFP2000 Series 
 
 
5-6
Frame B 
 
Main circuit terminals: 
z  If you install at Ta 40°C above environment, please select copper wire 
which have voltage rating 600V and temperature resistant 90°C or above.
z  If you install at Ta 40°C environment, please select copper wire which 
have voltage rating 600V and temperature resistant 75°C or 90°C. 
z  For UL installation compliant, you have to use copper wires when 
installation, the wire gauge is based on temperature resistant 75°C which 
is according to the requirements and recommendations from UL. Do not 
reduce the wire gauge when using higher temperature wire. 
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,  , B1, B2, DC-,DC+ 
Models  Max. Wire Gauge Min. Wire Gauge  Torque 
VFD110FP4EA-41/52
6 AWG [13.3mm
2
]
8 AWG [8.4mm
2
] 
M5 
25kg-cm 
[21.7 lb-in.]
[2.45Nm] 
VFD150FP4EA-41/52
VFD185FP4EA-41/52
6 AWG [13.3mm
2
] 
VFD220FP4EA-41/52
;  It needs following additional terminal when wiring.    The additional 
terminal dimension should comply with the following figure 1.
 
;  After crimping the wire to the ring lug (must UL approved), UL and CSA 
approved R/C(YDPU2) heat shrink tubing rated min 600Vac insulation 
shall be install over the live part. 
 
A 
(MAX) 
B 
(MAX)
C 
(min)
D 
(MAX)
d2 
(min)
E 
(min) 
F 
(min) 
W 
(MAX)
T 
(MAX)
23.8 6.0 13.3 9.0  5.3 11.0 13.3 12.0 1.5 