Set-Up and Use
7.11.3 Anti-Bacteria (Anti-Bact)
Factory Setting = No
- No legionella cycle except the return from vacation
and during exit frost over 3 days.
- During the legionella cycle the water temperature is
raised to 60°C by the heat pump.
- If the hot water is already set to 60°C (See Section
7.6) then legionella cycle will not run as
temperature is already obtained.
- If a cycle is interrupted by loss of electrical power
then the cycle will run at the next cycle period.
- The frequency of day can be adjusted according to
number of days
-During the anti-legionellosis cycle the temperature is
raised between 55°C and 70°C
ANTI-BACT
No
ANTI-BACT
8
Enter
Example:
Anti-Bact 8 = the legionella
cycle every 8 days
7.11.4 Fan Mode
Fan Vent
Fan Vent
2
Select Mode
Enter
Factory Setting = 1
- Mode 1 = Standard mode, automatic ventilation.
- Mode 2 = Manual mode, forced ventilation.
- Mode 3* = Ventilation during the heating of the
water and ventilation controlled by thermostat.
Thermostat is connected to input of the electronic card
in the heat pump water heater (see wiring diagram).
* In the case of activation of the PV mode, controlled
ventilation (Mode 3) is not available.
* The electric back-up immersion heater will activate
until the water temperature reaches 43
o
C. The heat
pump will complete the remaining charge to set
temperature.
7.11.5 Minimum Temperature
T
o
C Min.
No
T
o
C Min.
43
o
c
Select Mode
Enter
It is possible to allow the operation of the immersion
heater along with the heat pump to prevent the
water temperature falling below a minimum comfort
temperature of 38°C. The immersion will then heat the
water to 43°C, once this temperature has been reached

the complete heating of the water heater.
- By default this is not active.
- In case of load shedding, the function <T
o
C Mini> is
not active.
7.11.6 Shedding
You can select which items are restricted from running
during load shedding (immersion heater or heat pump).
Shedding
1
Shedding
0
Select Mode
Enter
- Press ‘Menu’ to return to the main screen.
If the power contact is open:
- Mode 0 = Nothing is allowed to run.
- Mode 1 = Only the heat pump will operate.
- Mode 2 = Heat pump and boost are will operate
(neutralising the peak hours).
If the PV function is activated then the load shedding
from the voltage-free contact (Entrée 1/2) is not
possible. In this case it is necessary to go through the
programme scheduling (See Section 7.10).
- Press ‘Menu’ twice to return to the main screen.
- Press ‘Menu’ twice to return to the main screen.
- Press ‘Menu’ to return to the main screen.
Example:
ANTI-BACT=8,
TEMP.WATER=60C
the anti-legionellosis cycle
will run every 8 days at 10pm