Trimmer Description
TC
0 s Disabled
120 s
Setting automatic closing time. From 0 to 120 s.
With DIP2=OFF, once a safety switch has been activated, the counter starts as soon
as the safety switch is released (for example after passing through the photocells),
and lasts for a period of time set with trimmer TC (50%).
With DIP2=ON, the counter starts when automation is opened and lasts for the entire
duration set with trimmer TC (100%).
NOTE: after the activation of the stop command, once contact 1-9 has closed again,
automatic closing is only enabled after a total, partial or step-by-step opening com-
mand.
TR
0 s
3 s
30 s
20 s
10 s
Setting motor 1 (M1) closing delay time. From 0 to 30 s.
When closing, motor 1 (M1) arrives after a delay set with trimmer TR relative to motor
2 (M2).
When opening, motor 2 (M2) starts after a delay of 3 s relative to motor 1 (M1).
With TR=MIN the door wings start simultaneously.
NOTE: setting TR=MIN with non-overlapping door wings and setting TR>3 s with
overlapping door wings is recommended.
RP
10% 100%
Motor 1 (M1) partial opening adjustment.
Adjust the percentage of partial opening of motor 1 (M1) from 10% to 100% of the total
operation.
VM
min max
Operation speed adjustment.
Adjusts the automation operation speed.
The closing speed is the same as the opening speed.
M1-M2
5 s 30 s
Motor 1 (M1) operating time adjustment. From 5 s to 30 s.
Motor 2 (M2) operating time adjustment. From 5 s to 30 s.
(or from 5 s to 45 s depending on the settings in paragraph 6.4).
The opening/closing operation is shown in chapters 11, 12 and 13: the operation con-
sists of a part with the speed set with trimmer VM, the duration set with trimmer M1/
M2 and deceleration to a ¿xed speed when both opening and closing.
When opening, this deceleration lasts a maximum of 10 s and when closing, it lasts
until the mechanical stop or a stop limit switch is reached (with FC=OFF).
R1
min max
Force adjustment.
The control panel is ¿tted with a safety device which, when it detects an obstacle:
- during opening, stops movement with a disengagement operation;
- during closing, before deceleration, inverts movement;
- during closing, during deceleration with FC=ON stops movement and with FC=OFF
inverts movement.