IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 5 di 38
6.2 Icon Dedicated to the Alarm Read-Outs
The following four icons are dedicated to a better alarm
understanding:
Generic Alarm
High pressure alarm
Low pressure alarm
Water flow Alarm
7. SILENCING THE BUZZER
Automatically: just after the alarm condition is recovered.
Manually
: push and release one of the four keys; the
buzzer is stopped even if the alarm is still active.
8. FIRST INSTALLING
After giving power supply to the instrument, the left lower
display can show “rtC” alternated with the probe value: it is
necessary to set the clock time.
If the probes are not connected, or they are faulty, the
display shows the corresponding alarm code.
In any case it is possible to proceed with the parameter or
clock setting.
9. HOW TO SET THE CLOCK RTC
1. Push the M key for some seconds and wait until the
“Hour” label appears. Release the M key.
2. Now push SET: the hour value starts blinking.
3. Use the
n and o to change the value. Confirm by
pushing SET; After some seconds the controller will
show the next parameter (Min).
4. Repeat the points 2 and 3 to set the other
parameters:
Min: minutes (0÷60)
UdAy: day of the week (Sun = Sunday, Mon = Monday,
tuE = Tuesday, UEd = Wednesday, tHu = Thursday, Fri
= Friday, SAt = Saturday).
dAy: day of the month(0÷31)
MntH: Month (1÷12)
yEAr: Year (00÷99)
10. HOT KEY PROGRAMMING
10.1 Download from the Hot Key (previously
programmed) to the Instrument Memory
The controller power supply is off:
Insert The Hot Key.
Turn the power supply on.
The download starts and lasts some seconds.
During this phase the whole regulation is locked and the
dOL” message is blinking.
When finishing the “End “ message will appear if the
programming result is good, after 15s the regulation
automatically restarts
If “Err” message appears the operation has given bad
result. Turn the controller off and then on again to repeat
the operation or restart the normal regulation.
10.2 Upload the Parameter from the Controller to
the Hot Key
The instrument is on:
1. Insert the Hot Key.
2. Enter the function menu.
3. Select the UPL function with the arrow keys.
4. Push SET key. The Upload starts immediately from
the instrument to the key memory.
During this phase the whole regulation is locked and the
UPL” message is blinking.
When finishing the “End “ message will appear if the
programming result is good, after 15s the regulation
automatically restarts
If “Err” message appears the operation has given bad
result. Repeat the points 1-4 for a new Upload.
11. KEYBOARD PROGRAMMING
To allow an easier identification of parameter meaning, the
parameters of the controller have been collected in different
families each one named with a peculiar label.
11.1 “Pr1” Programming Level (User Level)
To enter the “Pr1” User Level:
1) Push the SET +
n key for some seconds ( and
Leeds start blinking) the upper display shows
“ALL” that is the first family of parameters.
2) Using
o and n arrows scroll the other family labels.
3) After finding the right one, push SET key to enter and
see all the parameter belonging to that family, the
display shows the first parameter label and its value.
Scroll the parameter list with
o and n arrows or modify the
value as described in 11.4.
11.2 “Pr2” Parameter Level (Factory Level)
The “Pr2” parameter level is accessible through password: