IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 27 di 38
37. PARAMETER TABLE
SUB MENU SELECTIONS
LABEL Meaning
ALL Shows the whole set of parameters
ST It contains only the regulation parameters
CF It contains only the configuration parameters
SD It contains only the dynamic Set point parameters
ES It contains only the Energy Saving parameters
CO It contains only the compressor parameters
FA It contains only the fan regulation parameters
Ar It contains only the anti freeze parameters
DF It contains only the defrost parameters
AL It contains only the alarm parameters
LG It contains only the logging parameters
PARAMETER DESCRIPTION
Regulation Parameters
Parameter Description Min Max Meas. Resolution
ST01 Summer Set point ST05 ST06 °C/°F
Decimal
integer
ST02 Summer differential
0.0
0
25.0
45
°C
°F
Decimal
integer
ST03 Winter Set point ST07 ST08 °C/°F
Decimal
integer
ST04 Winter differential
0.0
0
25.0
45
°C
°F
Decimal
integer
ST05 Minimum set point limit for ST01 (summer)
-40.0
-40.0
ST01
°C
°F
Decimal
integer
ST06 Maximum set point limit for ST01 (summer) ST01
110
230
°C
°F
Decimal
integer
ST07 Minimum set point limit for ST03 (winter)
-40.0
-40.0
ST03
°C
°F
Decimal
integer
ST08 Maximum set point limit for ST03 (winter) ST03
110
230
°C
°F
Decimal
integer
ST09 Regulation band
0.0
0
25.0
45
°C
°F
Decimal
integer
Pr2 Password 0 999