TROUBLESHOOTING
33
COMPRESSOR WILL NOT START
Power to the
Refrigeration system.
Compressor is
unplugged.
Plug compressor in outlet on
face of main wiring harness
distribution block.
Low voltage.
Check power
source.
Defective refrigeration
component (capacitor,
overload, relay).
Replace.
Defective compressor. Replace.
Troubleshooting Tip: Use a short 15 Amp extension cord and
plug the compressor directly into the wall outlet.
This will bypass the Electronic Controls.
Note: For Testing Purposes Only.
Electronic problem.
1. Check relay.
2. Harnessing.
3. Temperature Sensor or control.
4. Control Board.
Compressor will not start.