CellCom‑LTE‑V
Programming and Installation Guide Digital Monitoring Products
7
Fire (CellComF‑LTE‑V only)
Use a normally open output on a fire control panel to indicate a fire alarm. Program the zone on the communicator
with a zone name and fire zone type. When the output on the control panel turns on and trips the zone, a message
will be sent to an SCS‑1R or SCS‑VR receiver at the central station. The zone name programming can be used to
describe which control panel zone indicated a fire. See Figure5b.
Figure 5b: Wiring Diagram for Fire Zones 1‑4
Use 18-22 AWG for
Power Supply connection
Z3 +
Z4 +
Z4 -
GND
12VDC Aux. Output
+
-
Ground
Fire
Control Panel
The panel or separate power
supply must be 12 Volt Regulated
and Power Limited.
Z1 +
Z2 +
RESET
S1
LOAD
S2
PROG
S
N
+12 G Z1 Z2 Z4-Z4+GZ3 RTO2O1
RB
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
J8
J9
S1
S2
S3
1k ohm
MODEL
CellComSLC
1k ohm
1k ohm
1k ohm

Other manuals for DMP Electronics CellCom LTE-V Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics CellCom LTE-V Series and is the answer not in the manual?

DMP Electronics CellCom LTE-V Series Specifications

General IconGeneral
BrandDMP Electronics
ModelCellCom LTE-V Series
CategoryCell Phone
LanguageEnglish

Related product manuals