Evolution EV AC
10
4.4 ø80-125 concentric vertical duct for removal of combustion products and air intake (type
C
33
)
The removal of combustion products and air intake can be made using concentric Ø80 mm ducts
for the removal of combustion products and Ø125 mm ducts for the air intake, using the Ø80-125
vertical duct kit, code
CGAS000231.
The maximum length from the boiler for vertical ducts, including the kit terminal, is 12 metres.
Each 90° elbow, or two 45° elbows, will reduce the available length by 1 metre.
Vertical outlet kit∅80/125
Cod. CGAS000231
Black tile
80/125
Cod. CGAS000074
45º curve
80/125
Cod.CGAS000183
90º curve
80/125
Cod. CGAS000182
1m coaxial tube∅80/125
Cod. CGAS000184
Black tile ∅80/125
Cod. CGAS000075
Examples of installation:
L
≤
12 mts.