6500-065-J-7-18
28
Open Beam
Close Beam
Reversing Edge
(Wireless Optional)
1
ON
2 3 4
Edge/Beam Inputs (3 & 4) Note:
Open/Close Edge/Beam inputs will activate in EITHER direction of gate travel.
When using dual operators: a edge/beam can be connected from the primary gate to #3
and the secondary gate’s edge/beam can be connected to #4.
DIP-Switches MUST
be turned ON for each
connected device.
If the distance between an
entrapment or obstruction exists
less than 16” from the open gate,
then entrapment protection is
REQUIRED for this area.
Entrapment protection
is RECOMMENDED for
this area.
OB
CB
OE
CE
G
G
1
ON
1477-010
SW1
2 3 4
4.3 Entrapment Protection Wiring
1
ON SW1
2 3 4
REVERSE
LOOP
P2 P8
EXIT
LOOP
LMT
POWER
NC
TIME
DELAY
NO
REV SENSE
PRIMARY
4405-018
REV SENSE
SECONDARY
2
4
5
6
7
8
20
1
ON SW2
2 3 45 6 7 8
OB
CB
OE
CE
G
G
1
ON
1477-010
SW1
2 3 4
1
2
3
4
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Notes:
ONLY connect monitored devices.
The 6-pin terminal can be unplugged from
circuit board for easy wire connections.
LED Notes:
LED OFF:
appropriate
device is
connected.
LED ON:
device has
been
activated.
Flashing LED:
Device NOT
connected.
Not
appropriate
device.
6-Pin UL 325 Terminal
Entrapment Protection Device Connection
OPEN Beam STOP (Switch 1)
CLOSE Beam REVERSE (Switch 2)
OPEN Edge/Beam REVERSE (Switch 3)
CLOSE Edge/Beam REVERSE (Switch 4)
Ground (Common)
Ground (Common)
OB
CB
OE
CE
G
G
1
2
3
4
5
6
Open Beam
OPTIONAL Wireless Note: Refer to the instruction sheet
that comes with the receiver/transmitter for more specific
wiring and mounting instructions.
To Com
To Edge/Beam Input
UL 325 DIP-Switches
To 24 VAC
To Com
Monitored Device Note: Only 1 monitored
Device can be connected to each input. An
OPTIONAL Expansion Board (sold separately)
will allow connection for additional devices.
P
U
S
H
T
O
O
P
E
R
A
T
E
t
e
c
h
ni
c
i
a
n
u
s
e
o
n
l
y
(2) Two 115 VAC
Convenience Outlets
1
2
3
4
5
6
Main Terminal #3 Note:
Exceeding 250 mA of power from this terminal
may cause the circuit board transformer to
overheat, causing intermittent problems.
Entrapment Protection must be provided for the gate
system where the risk of entrapment or obstruction
exists. The operator will not run without one or more
monitored type B1 or B2 entrapment protection devices
in EACH entrapment area.
24 VAC
Wireless Receiver
for Reversing Edge
Receiver MUST monitor
for the presence of the
transmitter.
IMPORTANT: Photo sensors must use Normally Closed (NC) contacts
with the beam set for light operate (relay activated when beam is not
obstructed). Some manufacturer’s photo sensor contacts are labeled as
Normally Open (NO) but their relay functions the same way as described
above. See specific manufacturer’s wiring manual for more information
about their specific relay function.
Type of wiring to be used on ALL external devices:
A) Type CL2, CL2P, CL2R, or CL2X.
B) Other cable with equivalent or better electrical,
mechanical, and flammability ratings.