Cooling
Enough free space shall be left around the inverter to ensure sufficient air circulation and
cooling. You will find the required dimensions for free space in the table below. If several
units are mounted above each other the required free space equals
space B + space C
(see figure on next page). Moreover, the outlet air used for cooling by the lower unit must
be directed away from the inlet air to be used by the upper unit.
Dimensions - inches (mm)
Cooling
air
required
FT
3
/min
(CFM)
Inverter type
XTdor XTe-
Frame
size
A
Distance
from one
inverter to
the next
B
C
4004 1 .787 (20) .394 (10) 3.94 (100) 1.97 (50) 41.20
4005 1 .787 (20) .394 (10) 3.94 (100) 1.97 (50) 41.20
4009 1 .787 (20) .394 (10) 3.94 (100) 1.97 (50) 41.20
4012 1 .787 (20) .394 (10) 3.94 (100) 1.97 (50) 41.20
4016 2 .787 (20) .394 (10) 4.72 (120) 2.36 (60) 111.83
4022 2 .787 (20) .394 (10) 4.72 (120) 2.36 (60) 111.83
4031 3 .787 (20) .394 (10) 4.72 (120) 2.36 (60) 111.83
4038 3 1.18 (30) .394 (10) 6.29 (160) 3.15 (80) 250.15
4045 3 1.18 (30) .394 (10) 6.29 (160) 3.15 (80) 250.15
4061 3 1.18 (30) .394 (10) 6.29 (160) 3.15 (80) 250.15
4072 4 1.18 (30) .394 (10) 6.29 (160) 3.15 (80) 250.15
4087 4 2.95 (75) 2.95 (75) 11.81 (300) 3.94 (100) 250.15
4105 4 2.95 (75) 2.95 (75) 11.81 (300) 3.94 (100) 250.15
4140 5 2.95 (75) 2.95 (75) 11.81 (300) 3.94 (100) 382.58
4168 5 2.95 (75) 2.95 (75) 11.81 (300) 3.94 (100) 382.58
4210 6 2.95 (75) 2.95 (75) 11.81 (300) 3.94 (100) 450.00