Mechanical brake control
The brake is controlled so that during starting the motor first generates torque and after that the
brake is opened. The same applies for stopping; while the brake is being closed, the motor still
generates torque. During a direction change, the brake is kept open all the time. XT Drive
decelerates the motor to a stop according to the set deceleration time when the run command is
switched off, so the brake is used only as a holding brake. This way brake wear is minimized. Only
if a failure occurs or the emergency stop button is pushed, the brake closes immediately stopping
the motor and the load.
The motors of CXT-hoists and SM-trolleys have an electromechanical disk brake. The disk brake is
opened and kept open during run by DC-voltage. When there is no voltage present the brake is
closed and also kept closed by spring force.
2-phase AC
- 002-045F
XT Scalar models 002F-045F include an AC-supply from two phases for
the disk brake control. XT Drive controls this line and it is protected by
an adjustable circuit breaker (max.4.0A). A rectifier included in the motor
rectifies the AC-voltage to DC-voltage brake coils.
REC12
- 002-011F
XT Vector models 002F-011F have a built-in REC12 brake control unit,
which is a line voltage half-wave rectifier (max.1.25Adc). The half-wave
type rectifier reduces losses and is enough to open the brake. There is a
contactor to switch the line voltage on and off. An external control unit is
needed to control other brake types.
ESD141
- 015-110F
XT Vector models 015F-132F have a built-in ESD141 brake control unit,
which is a line voltage full/half-wave rectifier (max.1.25Adc). Full-wave
rectification is used to open the brake quickly. Then, the rectifier
changes to a half-wave type, which reduces losses, but is enough to
keep the brake open. There is a contactor to switch the line voltage on
and off. The same contactor also disconnects the DC-voltage directly
from the brake coil, which guarantees that the brake closes fast. An
external control unit is needed to control other brake types.
3-phase AC
- 055-110F
- 055-110F
XT Drive models 055F-132F include a 3-phase AC-supply for the brake
control. XT Drive controls this line and it is protected by an adjustable
circuit breaker (max.4.0A). When a shoe brake is used, brake closing is
speeded up by capacitors. They are connected in parallel with the brake
via the brake contactor NC-contacts. The connection is partially ready in
XT Drive. Only the capacitors must be added outside XT Drive. This
connection can also be used to control 2-phase disk brakes or a
separate KA372B brake control unit.