Appendix 4: Regulatory Approvals
Important Notes for EN50131-1 compliant systems
The HS2128, HS2064, HS2032, HS2016 Control Panel has been certified by Telefication according to EN50131-1:2006
+A1:2009, EN50131-3:2009, EN50131-6:2008 (Type A) and EN50136-1:1997 (ATS2) for Grade 2, Class II.
For EN50131 compliant installations, with alarm control panels HS2128, HS2064, HS2032 and HS2016, only the intrusion
portion of the alarm system may be activated.
For EN50131 compliant installations the following functions have to be disabled:
l Fire Alarm,
l CO Alarm
l Auxiliary (Medical) Alarm functions
For EN50131 compliant installations the following zone types shall not be used:
007 Delayed 24-Hour Fire
008 Standard 24-Hour Fire
025 Auto Verified Fire
027 Fire Supervisory
040 24-Hour Gas
041 24-Hour CO
045 24-Hour Heat
046 24-Hour Medical
047 24-Hour Emergency
048 24-Hour Sprinkler
049 24-Hour Flood
052 24-Hour Non-Alarm
056 24-Hour High Temperature
057 24 Hour Low Temperature
071 Door Bell
In this configuration there are no non-mandatory events generated in the event buffer and compliance with minimum 250
events mandatory events storage (Grade 2) is ensured as per Section 8.10.1 in EN50131-3. Compliance labeling should be
removed or adjusted if non-compliant configurations are selected.
UK Compliance Statement
In the UK this product is suitable for use in systems installed to conform to PD 6662:2010 at Grade 2 and environmental class 2 with the following
notification options: A, B, C, D, X.
- 211 -

Table of Contents

Other manuals for DSC HS2016

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC HS2016 and is the answer not in the manual?

DSC HS2016 Specifications

General IconGeneral
Mounting TypeWall mount
Power Supply16.5VAC
Battery Backup12VDC
Operating Temperature32°F to 120°F (0°C to 49°C)