Appendix 4: Regulatory Approvals
Each of the above examples is under the sole responsibility of a single owner. The bell and DACT power supply must be in a protected area including partitioned sys-
tems. The bell and DACT power supply must be located where it can be heard by the person or persons responsible for maintaining the security system during the
daily arming cycle.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the person operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
The local control unit and the local power supply must be protected in one of the following ways:
l The control unit and audible alarm device must be in a protected area which is armed 24 hours a day.
l Each partition must arm the area protecting the control unit and the audible alarm device power supply. This may require duplicate protection armed by each
partition. Access to this protected area, without causing an alarm, will require that all partitions be disarmed.
l In all cases described above, the protected area for the control unit must be programmed as not-bypassable.
Casual Users
The installer should caution the user not to give system information (e.g., codes, bypass methods, etc.) to casual users (e.g., service people) and to only give out
One-Time Use codes.
User Information
The installer should advise the user and note in the User’s Manual:
l Service organization name and telephone number
l The programmed exit and entry time
l Instructions to test system weekly
l Note that the installer code cannot arm or disarm the system
4.1 SIA False Alarm Reduction Installations: Quick Reference
Minimum required system consists of one Control unit model HS2128 or HS2064 or HS2032 or HS2016-4 and any one of
the compatible listed keypads: HS2LCDRF9, HS2LCDRFP9, HS2ICNRF9, HS2ICNRFP9, HS2LCD, HS2LCDP, HS2ICN,
HS2ICNP, HS2LED HS2TCHP.
The following wireless keys can also be used in SIA compatible installations: PG9929, PG9939,PG9949.
Note: For models PG9929 and PG9939, the panic/emergency key shall be disabled for SIA compliant installations.
For a list of the default values programmed when the unit is shipped from the factory, and for other programming information,
refer to the following table.
The following optional subassembly modules also bear the SIA CP-01-2010 classification and may be used if desired:
HSM2108 zone expander, HSM2208 PGM output module, HSM2300 auxiliary power supply, HSM2204 output module,
HSM2HOST9 2-way wireless transceiver, PG9901 indoor siren, PG9911 outdoor siren, and 3G2080(R)/ TL2803G(R)/ TL280
(R) cellular and PSDN communication module.
Caution
l For SIA FAR installations use only modules/devices that are listed on this page.
l Fire Alarm Verification feature (Auto Verified Fire Zone type [025]) is not supported on 2-wire smoke detectors zones,
model FSA-210B(T)(S)(ST)(LST)(R)(RT)(RD)(RST)(LRST). This feature may be enabled for 4-wire smoke detectors
only (FSA-410B(T)(S)(ST)(LST)(R)(RT)(RST)(LRST) and wireless detectors PG9916/PG9926). The fire alarm delay
is 60s.
l Call Waiting Cancel (Section [382], option 4) on a non-Call Waiting line will prevent successful communication to the
supervising station.
l All system smoke detectors must be tested annually by conducting an Installer Walk Test. Prior to exiting Walk Test
mode, a sensor reset must be done on the system, [*][7][2], to reset all latching 4-wire smoke detectors. Refer to the
installation instructions supplied with the detector for details.
Notes
l Programming at installation may be subordinate to other UL requirements for the intended application.
l Cross zones have the ability to individually protect the intended area (e.g. motion detectors which overlap).
l Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.
l This control panel has a communication delay of 30 seconds. It can be removed or increased up to 45 seconds by
the end user with installer consultation.
l The system shall be installed with the sounding device activated and the communicator enabled for transmission
using SIA or CID format.
l ULC commercial burglary installations require DEOL resistors.
- 207 -