Section 5: Programming
l siren 01 – 16
l repeater 01 – 08
OFF – does not activate if an RF delinquency condition is present.
13 – Module Supervisory
ON – activates if any of the following module supervisory troubles is detected:
l HSM2HOST
l keypad 01 – 16
l zone expander 01 – 15
l HSM2204 1 – 4
l HSM2300 1 – 4
l HSM2208 01 – 16
OFF – does not activate if a module supervisory trouble is detected.
14 – Module Tamper
ON – activates if any of the following module tamper conditions is present:
l HSM2HOST
l Keypad 01 – 16
l Zone expander 01 – 15
l HSM2204 1 – 4
l HSM2300 1 – 4
l HSM2208 01 – 16 tamper troubles
OFF – does not activate if a module tamper condition is present.
15 – Communications
ON – activates if any of the following communications conditions is present:
l TLM trouble
l FTC receiver 1 – 4
l SIM Lock trouble
l Cellular Trouble
l Ethernet Trouble
l Receiver 1 – 4 absent
l Receiver 1 – 4 supervision trouble
l SMS Configuration trouble
l Alt comm. Fault.
OFF – does not activate if a communications trouble condition is present.
16 – Not Networked
ON – activates if any of the following not networked conditions is present:
l Zone 001 – 128
l Keypad 01 – 16
l Siren 01 – 16
l Repeater 01 – 08
l User 01 – 1000 (wireless keys) not networked troubles
OFF – does not activate if a not networked trouble condition is present.
156 – Latched System Event
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
02 – Timed Output / Latched Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
04 – Fire Alarm
ON: activates with fire alarm, [F] key, fire zones, 2-wire smoke.
OFF: does not activate with fire alarm.
- 82 -