Section 5: Programming
OFF: When a non 24-hour zone is bypassed in [*][1], the system logs and communicates the bypass status of the zone only
after the partition is armed. This option is applied regardless of how zones are bypassed in [*][1], recall bypass group, clear
all bypasses, bypass open zones, bypass recall as well as other methods such as bypassing via ITv2 or DLS.
Global Zones: 24-hour zone bypasses are logged and communicated in real time. Non 24-hour zone bypass events are
logged and communicated when armed. Non 24-hour zone unbypass events are logged and communicated when the last
partition is disarmed.
3 Armed Status PGM ON at End of Exit Delay
ON: PGMs are activated at the end of exit delay. This applies to PGMs with one of the following armed status attributes:
l 115 System Armed Status PGM
l 116 Away Armed Status PGM
l 117 Stay Armed Status PGM
l 120 Away Armed with No Zone Bypass Status
l 129 Partition Status Alarm Memory
OFF: PGMs are activated at the beginning of exit delay. This applies to PGMs with one of the armed status attributes listed
above.
4 Not Used
5 Keypad Buzzer Follows Bell
ON: The keypad buzzer activates with all bell activity for the selected partition.
OFF: The keypad buzzer only activates with alarms programmed to do so.
6 Not Used
7 Exit Delay Restart
ON: Opening a delay zone door after it has already been opened and closed during an exit delay restarts the exit delay
timer. Further openings and closings do not restart the timer.
OFF: Delay zone openings and closings do not restart the exit delay.
8 AC Fail Trouble Beeps
ON: System keypads beep when an AC trouble event occurs.
OFF: System keypads are silent during AC troubles.
[019] System Option 7
1 Audible Wireless Device Fault
ON: If a wireless zone fault occurs while armed, the siren sounds for the duration of Bell Time Out. This option only affects
zone definitions that are considered armed. The following zone types do not generate an alarm when faulted while stay
armed: interior stay away zone, delay stay away zone, instant stay away zone, night zone. The following zone types do not
generate an audible alarm in any armed state (stay, away, or night): 24-hour supervisory, 24-hour non-alarm, 24-hour CO,
delayed 24-hour Fire, standard 24-hour fire, Auto-verified fire.
When the partition is armed, wireless supervisory troubles from sirens, keypads and repeaters generate audible alarm con-
ditions.
If Tamper/Fault Detection is enabled, these events can start the burglary verified timer and affect the burglary verified
counter.
OFF: Wireless device faults do not sound the siren.
2 Latching Troubles
ON: Troubles remain on the system until viewed via [*][2], even if they are restored. The trouble condition is cleared when the
[#] key is pressed from the [*][2] menu after the trouble has restored. The Trouble LED turns off unless other troubles are
present. The trouble is not cleared if the [*][2] menu times out before the [#] key is pressed.
OFF: Troubles are cleared once restored.
3 Not Used
4 R Button
ON: When the panel goes off hook to communicate, it performs a dial tone check. If no dialtone is detected, the panel will
wait 20 seconds and perform another 5 second dial tone search. If dial tone is still not present, the panel force dials if pro-
grammed to do so. This entire sequence counts as one dialing attempt.
OFF: If no dial tone is present, the panel does not attempt to switch to a second phone line.
- 91 -

Table of Contents

Other manuals for DSC HS2016

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC HS2016 and is the answer not in the manual?

DSC HS2016 Specifications

General IconGeneral
Mounting TypeWall mount
Power Supply16.5VAC
Battery Backup12VDC
Operating Temperature32°F to 120°F (0°C to 49°C)