Note: For UL/ULC installations, bit 5 (PowerLED) and bit 6 (Power LED Indicates AC Present)
shall be ON.
[023] Third Keypad Options
Default Value Option ON Off
OF I__I 1 ArmedLEDPowerSave ArmedLEDOff inSleepMode
ON I__I 2 KeypadStatus Shows StayArm
KeypadStatus Shows Stay/Away
Arm
OFF I__I 3
5thTerminal is KeypadPGM Out-
put
5thTerminal is KeypadZoneInput
OFF I__I 7 LocalDisplay of Temperature NoLocalDisplayof Temperature
OFF I__I 8 LowTemperatureWarningEnabled LowTemperatureWarningDisabled
[030] Download LCD Messages
I___I___I___I___I___I___I___I___I___I___I___I___I___I ___I
I___I___I___I___I___I___I___I___I___I___I___I___I___I ___I
[031] Download LCD Message Duration
Default: 000 I___I___I___I
(Valid entries are 000-255, 000=Unlimited Msg Display) This number represents the
number of times the downloaded message must be cleared before it is permanently
removed. This message can be cleared by pressing any key.
[041] Indoor Temperature Zone Assignment
Default: 000 I___I___I___I
(Valid entries are 000-128)
[042] Outdoor Temperature Zone Assignment
Default: 000 I___I___I___I
(Valid entries are 000-128)
[101] - [228] Door Chime for Zones 1 - 128
The keypad can be programmed to make up to four different chime sounds for individual
zones (e.g., for Zone 1, enter section [101], for Zone 2 enter section [102]).
Default: 01 I___I___I
Valid Entries
01 6Beeps
02 Bing-Bingtone
03 Ding-Dongtone
04 Alarm tone (4 secondduration)
05 Zonename
[991] Reset Keypad Programming to Factory Defaults
1.
Press [*][8][Installer Code].
2.
Enter [991].
3.
Use the [<][>] keys to scroll to the applicable keypad.
4.
Press [*] to select the keypad.
5.
Re-enter [Installer Code].
6.
Press [*] to reset the selected keypad to factory defaults.