P R O G R A M D E S C R I P T I O N S
40
5.31.2 Factory Default Main Panel (Software) and other Modules
Step 1 - Enter the Installer Programming mode. Step 3 - Enter the Installer Code.
Step 2 - Enter Program Section [XXX]. Step 4 - Enter Program Section [XXX] again.
The panel will take a few seconds to perform the default. When the keypad is again operational the default
is complete.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Restore LINKS2X50 to Factory Default Programming ........................ Section [993]
Restore Escort5580 to Factory Default Programming ......................... Section [995]
Restore PC5132 to Factory Default Programming .............................. Section [996]
Restore PC5400 to Factory Default Programming .............................. Section [997]
Restore PC5928 to Factory Default Programming .............................. Section [998]
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Restore Main Panel (Software) to Factory Default Programming ....... Section [999]
5.32 Installer Lockout
If Installer Lockout is selected a hardware default cannot be performed. If a software default is
performed all programming will restore to factory default.
When Installer Lockout Disable is selected the panel will restore all programming to factory defaults if a
hardware or software default is performed on the main control panel.
To enable or disable Installer Lockout perform the following:
Step 1 - Enter Installer Programming. Step 3 - Enter the Installer Code.
Step 2 - Enter Program Section [XXX]. Step 4 - Enter Program Section [XXX] again.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Installer Lockout Enable ......................................... Section [990]
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Installer Lockout Disable ........................................ Section [991]
5.33 Walk Test (Installer)
The Installer Walk Test can be used to test the alarm state of each zone of the panel. The walk test
cannot be used to test zone type [24].
Before beginning the walk test, ensure the following conditions are met:
1.The panel is disarmed
2.The Keypad Blanking option is disabled (section [016]: [3])
3.The Fire Bell is Continuous option is disabled (section [014]: [8])
4.The Transmission Delay is disabled, if Transmission Delay is not required (section [370])
Fire Troubles are not supported in Walk Test.
To perform a Walk Test, do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Output for two seconds, log the event to the
Event Buffer and communicate the alarm to central station. Each zone should be tested several times
during the test. Check the event buffer to ensure that all zones and FAP keys are functioning properly.
To stop the test, you must do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
Check the Event Buffer after the Walk Test is complete, to ensure that the Audible/Silent 24-hr PGM
alarms have been restored.
The Alarm Memory is cleared upon entering Walk Test mode. When the Walk Test is complete, the
Alarm Memory light will remain lit, but there will be no alarms in memory. The light will turn off the
next time the panel is armed.

Table of Contents

Other manuals for DSC LCD5500Z

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC LCD5500Z and is the answer not in the manual?

DSC LCD5500Z Specifications

General IconGeneral
BrandDSC
ModelLCD5500Z
CategoryControl Panel
LanguageEnglish

Related product manuals