12
This works just like enrolling modules. You will be prompted
to ’Press Any Key On Desired Unit’ in the case of keypads
and ’Create Tamper on Desired Unit’ in the case of modules.
Once the correct action is taken, the keypad will display the
module number (e.g. LCD45XX Mod 02).
4.4 Enrolling AML Devices
Addressable Multiplex Loop (AML) devices use a 2-wire
connection for power and communication to and from the
control panel. All detectors are designed for low power
consumption to make for an efficient system.
For information on AML wiring, please see 2.9 ‘AML
Device Wiring‘.
Enroll the AML devices
after
all PC4108A, PC4164 and
PC4116 modules have been enrolled.
Programming the PGM Terminal for an AML Loop
Ref #: [001400]
To enroll addressable multiplex loop (AML) devices, you
must first program the PGM terminal you have selected for
the loop. Perform the following:
1. Enter Installer’s Programming and enter reference
number [001400].
2. To select PGM1 for AML devices, scroll to ’PGM1
AML?’ and press [*]. The option will toggle to Yes.
3. To select PGM2 for AML devices, scroll to ’PGM2
AML?’ and press [*]. The option will toggle to Yes.
NOTE: Do not turn off the PGM AML toggle option unless
all AML devices have been removed from the loop (see
’Removing AML Devices’).
To Enroll an AML Device
Ref #: [00140300] for PGM1
Ref #: [00140400] for PGM2
NOTE: All AML devices must be connected before they are
enrolled.
To enroll the device, perform the following:
1. FOR DEVICES TO BE ENROLLED ON PGM1: Enter
Installer’s Programming and enter reference number
[00140300].
FOR DEVICES TO BE ENROLLED ON PGM2: Enter
Installer’s Programming and enter reference number
[00140400].
2. Enter the 5-digit serial number on the detector to be
enrolled.
3. If the correct serial number was entered, the panel will
allow you to select the zone that the addressable detector
will be assigned to. Any zone from zone 001 to 128 on the
PC4020 can be used as an AML zone. If the detector is not
connected to the PGM terminal, the zone will not be
enrolled.
Do not use zones designated for Access Control.
Repeat from Step 2 until all AML devices have been enrolled.
If the zone serial number is already programmed into the
panel, the panel will display the message ’Already
Enrolled’ on the top line of the LCD and the serial number
on the bottom line of the LCD for three seconds. The panel
will then display the zone assignment for the device. This
allows for the reassignment of an existing zone or to verify
programming.
NOTE: Only the AMS-220/220T devices may be defined as
fire zones. Do not program other AML devices as fire zones.
AML Key
Ref #: [001401]
IMPORTANT NOTE: To ensure system security, the AML
Key must be programmed when using AML devices.
The AML Key is a 2-digit code that acts as a security lock
for the AML detectors. Once you have enrolled all AML
zones, you must change the AML Key from [00] to another
2-digit number (01-FF). When the AML Key is changed, the
panel broadcasts the new code to each addressable device.
Any device added to the system with a AML Key other
than the one programmed or the default [00] will not func-
tion.
When an addressable device is deleted, the panel repro-
grams the device’s AML Key to 00. This allows the device
to be re-enrolled on another system.
Moving AML Devices
To another zone on the same loop
1. FOR DEVICES TO BE MOVED ON PGM1: Enter
Installer’s Programming and enter reference number
[00140300].
FOR DEVICES TO BE MOVED ON PGM2: Enter
Installer’s Programming and enter reference number
[00140400].
2. Enter the device’s 5-digit serial number. The keypad
display will read ’Already Enrolled [
serial number
]’ to
indicate that the device has already been enrolled.
3. After three seconds, the display will indicate the
device’s zone assignment. Enter the new zone number.
Any zone from zone 001 to 128 on the PC4020 can be
used as a AML zone.
4. The zone definition and attributes must also be pro-
grammed for the new zone.
To another zone on a different loop
When moving devices to another loop, they must be
deleted from the first loop by following the instructions in
’Removing AML Devices’ (see below). The device’s serial
number can then be re-entered on the other loop as indi-
cated in ’To Enroll an AML Device’ (see above).
Removing AML Devices
Ref #: [00140301] for PGM1
Ref #: [00140401] for PGM2
When removing AML devices, they must be deleted from
the loop. If the device is not deleted, its AML Key will not
be reset to [00].
To remove an AML device from the system, perform the
following:
1. For devices to be deleted from PGM1: Enter Installer’s
Programming and enter ref# [00140301].
For devices to be deleted from PGM2: Enter Installer’s
Programming and enter ref# [00140401].
2. The display will read ’Serial# [ ]’ on the top line of the
display and the zone label on the bottom line of the dis-
play. Use the [<][>] keys to scroll to the zone to be
deleted then press [*]. The bottom line of the display
will then read ’Zone Deleted’.
3. To delete all AML devices from the selected PGM out-
put, select Default AML. The panel will display ’Con-
firm Default Press [*]’. To delete all AML devices on the
selected PGM, press [*].