Installation and Wiring
5
SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
mation regarding the various zone types, please see 5.4
‘Zone Programming‘.
Fire Zone
This zone type uses normally open contacts. The zone will
initiate a fire alarm when the loop is shorted (contacts close).
A Fire Zone trouble will be generated when the loop is
opened (wire break). Typically, fire alarm initiating contacts
originate from 4-wire smoke detectors. These types of detec-
tors must be wired as shown in the diagram below.
The power for the 4-wire detectors must be supervised with
an end-of-line relay (RM-1). The contacts of that relay are
wired in series with the zone end-of-line resistor. With the
relay energized, the relay contacts are closed and the zone is
normal. If the power is lost, the relay de-energizes, the con-
tacts open and a zone trouble is initiated.
Multiple fire initiating normally open contacts may be used
in parallel on the loop. Do not include burglary or other
types of devices on a fire zone.
NOTE: Minimum 18 AWG wire is required for Listed Resi-
dential Fire Alarm Systems.
Keyswitch Zone
Zones programmed as keyswitch arming zones must be
wired according to one the following diagrams:
LINKS Supervisory Zone
This zone is for use with a LINKS1000/LINKS2150/
LINKS2450 only. If the LINKS experiences a trouble condi-
tion, a LINKS output can be used to violate this zone type
and the event will be reported to the central station.
See the corresponding LINKS
Installation Manual
for wir-
ing information.
LINKS Answer Zone
This zone is for use with a LINKS1000 only. In case of a tele-
phone line failure, the panel can be uploaded/downloaded
via the cellular network. If the LINKS detects an incoming
call, it will activate an output that can be used to violate this
zone type. This will force the panel to answer the cellular call
and will begin communications with the downloading com-
puter. This zone must be programmed as LINKS Answer
and wired according to the following diagram:
AC Delay Zone
This zone is for use with a LINKS1000. If the LINKS experi-
ences an AC trouble condition, a LINKS output can be used
to violate this zone type and the event will be reported to
the central station.
See the corresponding LINKS
Installation Manual
for wir-
ing information.
2.8 Programmable Output
Wiring
The PGM output is a program-
mable terminal and will connect
to +12V when activated. The ter-
minal can source a maximum
current of 50mA. If the desired
current is higher than 50mA, a
relay will be required. To connect
the relay, refer to the above diagram. Each output can be
programmed as one of numerous available output options.
See 11.3 ‘Programmable Output Options‘ for a complete list
of PGM output options.
2.9 AML Device Wiring
Addressable Multiplex Loop (AML) devices use a 2-wire
connection for power and to communicate to and from the
control panel. All detectors are designed for low power con-
sumption to make for an efficient system.
The system can accommodate up to 128 addressable
devices. Connect the addressable loop to PGM1 and/or
PGM2, when programmed for AML operation. If only one
loop is used, then all 128 devices can be on the loop. If both
PGM1 and PGM2 are used, the 128 devices can be divided
between the two in any ratio that suits the application.
For instructions on configuring PGM1/PGM2 for AML
operation, and for AML device enrollment, see 4.4 ‘Enroll-
ing AML Devices‘.
NOTE: The panel must be powered down when adding or
removing devices from the AMLbus.
Addressable Devices
The following addressable devices are available:
• AMS-220/220T smoke detector with optional tempera-
ture sensor*
• AMB-300 PIR detector
• AMB-500 ceiling PIR detector
• AMB-600 dual PIR detector
• AMA-100 glass break detector
• AMP-700 magnetic door/window contact
• AMP-701 contact input module
• AMP-702 fire alarm contact input module
• AMX-400 repeater/isolator module
• AML-770 isolator module
*Fire alarm devices cannot be placed on the same loop as
burglary devices.